40-7705I-UM Page 89 Rev 4 March 16, 2007
• Select ALARM and/or ZREST plus desired Zones if Forwarding
Alarm data is the objective.
• Select as desired any other type of data or feature that you want
forwarded. The following options are available: In some cases the
only information forwarded is a message indicating that a packet of
the selected type was sent and not the data itself,
STAT → Subscriber Status
CHKIN → Check-In
DATA
HPBU → Programming Uploads
TEST Data
ZDATA → Zone Data
VLS → Vehicle Location Data
TEXT → Text Message
• Other Options: The following additional features can be activated
for forwarding. These require specific units and capabilities at the
Forwarded to site to be accepted and properly handled.
o Alarm Automation Message: Alarm activity can be
transmitted to the remote unit in Alarm Automation Format.
The RS-232 output of a special "FA" or "FAA" 7050-DLR
receiving unit can feed alarm data directly to a computer
running automation software. Sending these specially
formatted packets to a subscriber that is not intended to receive
it will cause the packet to be rejected.
o Relay Following: This special function requires the Forward-
To unit to be a 7050-DLR subscriber unit with a 7065 Relay
Output board installed. When programmed for forwarding
with relay following and a zone in alarm message is received
from the origin unit, a relay control command is sent to the
receiving unit to activate a relay. Zone 1 in the origin unit trips
relay 1 in the forward-to unit, zone 2 trips relay 2, and so on.
- For 7050 version 2 and later, the relay is momentarily
activated for 1 second. Be aware that the relay may activate
more than one time but should always return to a Normally
Open State
- r 7050 version prior to 2 the relay is toggled. Be aware that
you cannot be sure if the relay will be left open or closed.
Only that it will change state at least once.