40-7705I-UM Page 82 Rev 4 March 16, 2007
Zone Configuration window for the 7050 DLR/7750 UL Bank 1 - 8
Figure 11-18
The zone configuration control block offers seven options for the
programming of each alarm zone:
Normally Open Normally Open with Restoral
Normally closed Normally Closed with Restoral
Bypassed Supervised (Not available on Bank 0, Zone 1-8)
Supervised with Restoral. (Not available on Bank 0, Zone 1-8)
Use the mouse to select the appropriate boxes for the zone you wish to
program. Banks 1-8 support Supervised programming and wiring.
UL and COMMERCIAL FIRE INSTALLATION REQUIREMENTS for
7750/UL Subscriber Units:
Zones 1-6: Bypassed
Zone 7: N.O. w/Restoral–Tamper (creates N.C. loop through zone 7 of 7072 module)
Zone 8: N.O. W/Restoral – AC Fail (from 7072 multi-board)
Refer to Subscriber Unit Manual for details on zone wiring and
programming.